China Suppliers Factory Centrifugal Series Air Curtain Machines with Energy-Saving Heating Solutions and Durable Aluminum Fan Wheels
Install
1. The installation of the FM series and the RFM series is the same. Just loosen the positioning screws at the bottom of the front of the machine body, separate the machine body from the base plate, and then firmly fix the base plate on the door frame or the wall (if not fixed tightly, it will cause vibration and noise). Hang the machine directly on the base plate, and reinstall the loosened positioning screws on the base plate in the original position to fix the machine body.
2. The RFMS series water and heating air curtain machine should be installed on the indoor side of the door or window to prevent water from accumulating in the coil of the heat exchanger and freezing or cracking.
3. According to the different heat media selected, corresponding water supply and drainage pipelines should be equipped and insulated. If using hot water, the lower part should receive water and the upper part should return water. An automatic vent valve is required at the highest point of the main pipe.
4. Use softened water when using hot water as the medium.
5. Before operation, discharge condensate water or mixed gas in the heat exchanger. Preheat for 10 minutes before turning on the air curtain. When stopping, drain the water in the coil completely. If the temperature is below 0℃, the system must not stop heating.
6. During winter operation, the heat source must continuously supply heat to ensure the working state of the air curtain.
Operation and Maintenance
1. If any abnormal phenomena or noises occur during operation, stop the machine immediately for inspection.
2. Keep the interior clean. For RFM-II PTC and RFMS water-heated models, regularly clean dust from heaters and heat exchangers.
3. Inspect the machine after 1500 hours of cumulative use. Remove dust and oil stains using a neutral detergent. When cleaning the fan wheel, be careful not to deform the blades. Always cut off the power supply before cleaning.
4. In winter, if the water-heated air curtain is not in use, ensure water is drained or anti-freezing measures are taken to prevent the heater from cracking.